Prüffeld

Special container genset for the computing centre of a major bank in London

Emergency power diesel genset in soundproofed special container. The maximum sound level is approx. 62 dB(A) at a distance of 1 m with all 4 gensets operating.

The system is equipped with a redundant starting system and a fire-fighting system (water mist technology).

 

Back




4 x 2275 kVA 3516 BHD container gensets

Diesel engine Caterpillar
Type 3516 BHD
Output 1820 kW
Speed 1500 rpm

Generator Leroy Somer
Type LSA 53 UL 85/4p
Output 2275 kVA
Voltage 11000 V